This model is suitable where overhead tank capacity is small and underground tank capacity is large.
This model is suitable for the controlling the overhead tank water supply as soon as the overhead tank gets empty. The pump will start and the underground tank water will be lifted to overhead tank. The pump will be stop when the overhead tank gets full.
The controller has a protection for pump Dry run safety which senses the water reaching to overhead tank within the 60 seconds whenever pump starts. If the water is not reaching to the overhead tank within the specified time it trips the pump and gives audio visual alarm. Thus protecting the pump from damage. The audio visual alarm will be reset by the application of Reset switch & pump will start if dry run fault is rectified.
The controller has a redundant pump facility. One pump at a time will operate. In case of failure of first pump we can able to operate another pump. v
Model No | OHDOL2DR/23 |
---|---|
Control on | Overhead Tank |
Facia Indications | Power on/Pump on/Motor Dry Run Overhead tank level status |
Protections | Overhead tank Empty Motor Dry Run |
Dry Run Protection Time and control | 20 to 60 Seconds /Local Dry run Audio Alarm and motor trip automatically, Reset switch to restore the motor operation subject to clearance of Dry run |
Operation Mode | Auto / Manual |
Pump | Single Phase / Three Phase motor with starter/contactor |
Pump Selection | Single Pump |
Supportable Sensors | Float/Magnetic/ SS electrode |
Sensor Length | Max. 60mtrs without strong magnetic field |
Supply Voltage | 230V AC/50 Hz |
Sensing Voltage | 12V DC/0.12 Micro Amp |
Size | W X H X D 4.75 X 8 X 2.5 inch |
Mounting | Wall mounted type |
Cabinet | MS powder coated |
Assembling | Industrial grade components |